AFDD32 Arc flashover fire protectors

Referencia: AFDD32B06

http://www.maxge.eu/web/image/product.template/95/image_1920?unique=3b09ec6

• Operating voltage: 240V AC
Standards: GB/T31143 and EN/IEC 62606
Breaking capacity: 6000A
Operating frequency: 50Hz
Status indicator light
Local fault indication
Connection in box terminals for copper cables:
Rating =25A: flexible =16mm2 and rigid =25mm2
Rating 32÷63A: flexible =25mm2 and rigid =35mm2
Dimensions: 2 modules (36mm)
Detection of arcing in different circuits connected in series, parallel and earthed due to loss of insulation to earth due to loss of insulation caused by ageing, contamination or high humidity. The product trips and disconnects a protected circuit when arc faults are detected.
Arc protection in addition to overload and short-circuit protection.
Specifically indicates whether the fault has been caused by arcing, independently of overload and short-circuit.
Suitable for residential installations, or installations where it is essential to protect against electric arcs that could cause fire or damage to the installation.

Not Available For Sale